变流量双级压缩制冷系统实验研究 预览

Experimental Study on Variable-flow Two-stage Compression Refrigeration System
在线阅读 下载PDF
收藏 分享 导出
摘要 为改善变工况条件下,定频双级压缩制冷系统不能达到最佳状态运行的现状,本文搭建变流量双级压缩制冷系统实验台,分析了变工况条件下,低高压级压缩机输气量比对一次节流中间不完全冷却制冷系统性能的影响。结果表明:当冷凝温度为30℃,蒸发温度为-35~-20℃,低高压级压缩机输气量比由1.25增至3.33时,系统制冷量随着低高压级压缩机输气量比的增加逐渐减少,性能系数COP最大为2.37;当蒸发温度从-20℃降至-35℃,每降低5℃,最佳COP下的低高压压缩机输气量比依次增大22.10%、12.52%、14.29%。故实际系统设计时,可参考实验数据,根据不同蒸发温度和制冷量需求,调节合适的低高压级压缩机输气量比,使系统运行达到最佳状态。 The constant-frequency double-stage compression refrigeration system fails to run in the best state at the working or load changing conditions.To improve its performance,maintain the maximum performance coefficient,and achieve rapid and accurate cooling,a variable-flow double-stage compression experimental bench was set up.The proposed method was able to control the refrigerant gas flow rate of the low-pressure compressor and change the refrigerant mass flow rate.Therefore,the experimental study of two-stage compression cooling was conducted.Results showed that the refrigeration capacity of the system was decreased with an increase in the ratio of input gas of low-and high-pressure compressors(in the range of 1.25 to 3.33)at the condensation temperature of 30℃,evaporation temperature of-35--20℃.The cooling capacity of the system gradually was decreased with the increase of the ratio of input gas of low-and high-pressure compressors and the maximum coefficient of performance(COP)is 2.37.The ratio of input gas of low-and high-pressure compressor under the optimum COP was increased with the decrease of evaporation temperature.Considerably,as the evaporation temperature decreased by 5℃with the evaporation temperature of-35--20℃,the ratio of the input gas of the low-and high-pressure compressors under the optimal COP was increased by 22.10%,12.52%,and 14.29%,respectively.Therefore,for the actual system design,the experimental data can be used to adjust the ratio of input gas of low-and high-pressure compressors according to the different evaporation temperatures and refrigeration demands.
作者 杨永安 蒋春艳 武传志 罗建成 Yang Yongan;Jiang Chunyan;Wu Chuanzhi;Luo Jiancheng(Tianjin Refrigeration Engineering Technology Center,Refrigeration Engineering Research Center of Ministry of Education,Tianjin University of Commerce,Tianjin,300134,China)
机构地区 天津商业大学
出处 《制冷学报》 CAS CSCD 北大核心 2019年第5期136-142,共7页 Journal of Refrigeration
基金 国家科技支撑计划(2014BAK17B02) 国家自然科学基金(11572223)资助项目。
关键词 双级压缩 变流量 输气量比 COP two-stage compression variable flow ratio of input gas COP
作者简介 通信作者:杨永安,男,高级工程师,天津商业大学机械工程学院,+8613323322332,E-mail:yyan@tjcu.edu.cn。研究方向:制冷系统节能及优化。
  • 相关文献
投稿分析

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部 意见反馈